Ammeters of bi-metallic pattern commonly used for the indication of electricity demand.

Introduction
These indicators are surface mounted and have a completely insulated case. The cover is retained by two knurled insulated knobs, which can be sealed to the re-setting knob by a wire and seal if required. The re-setting knob is manufactured from a moulded insulated material and there is provision for a phase identification disc if required.

The thermal movement employed in the CL3 Instrument comprises a resistive temperature heating element and two bi-metallic coils, one for ambient temperature compensation and the other for actuation of the moving and slave pointers. The moving pointer, coloured black, will indicate load at any instant, continuously averaged over a period equal to the time lag. The slave pointer, coloured red, is driven by the moving pointer and will remain at its maximum reading where it is firmly held by a friction device until manually reset by an external knob on the front of the indicator.

Specifications
Movement Accuracy
Flat spiral bi-metal elements fully compensated against change in ambient temperature to give an accuracy of 3% of the full scale value.

Scale
The scale length is 67mm and is calibrated from 20% to 120% of the normal full load.

Power Consumption
6 VA at normal full load.

Time Lag
Indicators are available with time lags of -
20 minutes Pt. No. MFC-02644
30 minutes Pt. No. MFC-02645

Capacities
The CL3 indicators are designed for use with current transformers having 5 amp secondaries. The basic indicator has a maximum scale reading of 6 amps which allows a 20% overload on the nominal current.

20 or 30 min time lag
Reversible scale available

Surface mounted

Fully compliant with ESI 50-2

DOWNLOAD PDF